Skip to product information
Amana® PHWT-A200 Programmable Wired Thermostat

Amana® PHWT-A200 Programmable Wired Thermostat

SKU: PHWT-A200

About This Product

  • A variety of wired thermostats may be used with the Amana brand PTAC.
  • All thermostats offered can be connected to the PTAC through a low-voltage connection.
  • The Amana brand DigiSmart™ PTAC also offers a wireless remote thermostat.
  • Any thermostats other than those listed below or the DigiSmart thermostat must be submitted to Goodman for approval prior to use.


Specs & Details

SPECIFICATIONS

Model PHWT-A200
Type Programmable Electronic Thermostat
Input Voltage 19 to 30 VAC
Output Rating Max. 1.5A per terminal (3A total)
Temperature Control Range 45°F to 90°F (7°C to 32°C)
Temperature Accuracy ± 1°F (± 0.5°C)
Temperature Scale °F or °C
Temperature Calibration -5°F to +5°F (-3°C to +3°C)
Mounting Wall mount, about 5 ft above floor (on an inside wall)

WIRE TERMINALS

C 24 VAC Common
R 24 VAC Hot
Y Cooling Signal
W1 1st Stage Heating Signal
W2 2nd Stage or Auxiliary Heating Signal
GL Fan LOW Speed
GH Fan HIGH Speed
B/O Reversing Valve

COMPATIBILITY

Conventional PTAC (Amana PTC) Up to 1 Heat / 1 Cool, with or without electric heat
Heat Pump PTAC (Amana PTH & HEH) Up to 2 Heat / 1 Cool, with or without electric heat
Single-Speed Fan Units Supported (use GL terminal, High Fan set to OFF)

INSTALLER SETTINGS

Available Modes Heat/Cool/Auto
Heat/Cool
Heat Only
Cool Only
Max. Heat Set Point 60°F to 90°F (default 80°F)
Min. Cool Set Point 60°F to 80°F (default 65°F)
System Type Heat Pump or Conventional
HP Valve Type B (on in Heat) or O (on in Cool)
Auto Dead-Band 2.0°F, 3.0°F, 4.0°F, 5.0°F
Swing / Temp. Differential ±0.25°F, ±0.50°F, ±1.00°F, ±2.25°F
Aux. Stage Offset (Heat Pump) Off, 1.0°F to 5.0°F
High Fan Available or Disabled
Programming Manual or Programmable
Clock Format 12 hr (AM/PM) or 24 hr
Periods per Day 4, 2 or 1
Default Heat Set Temp 70°F (21°C)
Default Cool Set Temp 74°F (23°C)
Compressor Protection Bypass Installer test mode (auto-resets after 5 min)
Factory Reset Yes

DEFAULT PROGRAM SCHEDULE (4-PERIOD)

Morning – 6:00 AM Heat 70°F / Cool 78°F
Day – 8:00 AM Heat 62°F / Cool 82°F
Evening – 6:00 PM Heat 70°F / Cool 78°F
Night – 10:00 PM Heat 62°F / Cool 75°F